The possible errors that may occur when sending the set to the central device include:
"Timeout" => No response from device.
"Exception" => Value not accepted by device.
"Unknown" => Unknown error.
"Success" => Value sent with success.
The device name/address is shown in the "device" column.
3.4.6 XWEB5000 SUPERVISOR SYSTEM (ONLY XWEB5000)
The supervision concept significantly expands the possibility of intervention by the XWEB5000 on
system management. Supervision is intended as the ability of independent intervention by the monitoring
unit on the monitored devices. To simplify the concept, it may help to think of a functional block with all the
variables detected on the controller field (temperatures, pressures, operating status, alarms, etc...) as an
input, and as an output, the possibility of sending specific commands to the same controllers. The basic link
between input and output lies in the supervision, that is to say, in a special algorithm that the user has
programmed and that the system implements each time the input variables meet the set criteria. Pay due
attention to the fact that the sending of certain commands verified, following the establishing of certain input
conditions, is not accompanied by the sending of additional commands when the input conditions fail. In
other words, when the user considers and realises the direct action, the reverse action must then be
realised. Otherwise, the system is unable to restore the initial conditions when required.
Given the evident importance of this new work tool, Dixell has tried to make its usage as simple as possible
for the end-user. This is why the event is programmed through the graphic user interface, therefore, no
programming knowledge is required (in contrast with what occurs with normal programming languages for
PLC).
THE PROJECT
From a practical point of view, the user must be familiar with the supervision project to be realised in
advance, this is why, for educational purposes, the project considered throughout this chapter will be the
following:
the installation in question, demonstrates the need to monitor the operating state of an emergency generator
that is only activated should there be no electric energy supply. Upon the occurrence of this condition, the
supervisor must send a series of commands to the utilities in order to manage, at the highest possible level,
the energy saving function during a power-cut. In the example in question, the generator is monitored
through means of a Dixell XJA50D controller (alarm/status acquisition module): when the generator is
activated, the module signals this through the variation of the corresponding digital input. During operation
with an emergency generator, the XWEB-EVO must send the "energy saving" command (variation of work
set-point) and, only for the compatible utilities as well as the "save cold" curtain lowering command.
Page view 60