XWEB 500 – rel.1.0
APPENDIX A:
APPENDIX A:
DEVICE ADVANCED SECTION
DEVICE ADVANCED SECTION
In this section we describe how you can customize your device regardless its factory setup. We will point out
only the main sections, without describing each fields in deep. Please notice that the page is divided in many
rows. Each of them customizes a particular function of the device itself.
To access this section please stop data reading/recording, then go to “Configuration”->“Devices” roll-down
menu. Here with selection “Actions” roll-down menu choose “Advanced”, then with “Devices” choose the
proper controller.
“Analog Input” section shows you all the analog input that a device can use. These values can be displayed
in decimal or integer values, of course you have to choose the same unit of measurement for both the XWEB
and the instrument. The suffix-I” means you want to display integer, default value is decimal. The same for
Celsius and Fahrenheit degree. The suffix “-F” means Fahrenheit degree.
Warning: the integer/decimal or °C/°F configuration have to be chosen according to the real setting
of the instruments.
“Digital Input” row need particular attention. The values you find here are the factory defaults, so if you have
made modifications to the device setup, you are requested to apply the same modifications in this menu.
This is very important because all the values stored inside XWEB 500 devices section must be the same as
the ones stored inside the EEPROM of the instrument. A common error for example is to modify “Generic
Alarm” to some other values inside the instrument, than leave the value marked inside Advanced section.
XWEB 500 will send you an alarm every time the switch changes status, even if it is not a generic alarm.
“Device Status” section allows you to customize your instruments, of course the same values have to be set
both on XWEB 500 and the instruments themselves.
92/103 10/01/2006 - 1592010900